OUR PRODUCTSCLASSIFICATION

Continuous discharge, fixed discharge, and hydrophobic expansion vessel

 

continuous blowdown flash tank

1、 The purpose of continuous arrangement:
Continuous sewage expansion tank is used to expand and depressurize continuous sewage, separate it into steam, and utilize it to improve the thermal economy of power plants. It is connected to the continuous sewage outlet of the boiler and is used to expand and depressurize the continuous sewage of the boiler. The sewage is adiabatically expanded and separated into secondary steam and waste hot water in the continuous sewage expansion tank, and then discharged after expansion, depressurization, and heat exchange in the expander. The secondary steam is led out by a special pipeline, and the waste hot water is automatically discharged through a float level valve or overflow regulating valve. The thermal energy can be recovered and reused. The continuous discharge rate is automatically adjusted with the change of boiler feedwater load to maintain a relatively stable discharge rate. So utilizing secondary steam and waste hot water as heat sources can recover some of the heat lost during continuous boiler discharge and improve boiler efficiency.

2、 Composition structure:
1. Shell 2, inlet distributor 3, outlet steam demister
4. It consists of a safety release device 5, a liquid level display 6, and a liquid level adjustment device.
(The safety relief device and liquid level regulating device are not within the scope of supply. If they are required to be matched at the same time, they must be specified in the contract.)

3、 Main specifications and technical parameters:

Parameter model

Design pressure
MPa

Design Temperature

Working pressure
MPa

operation temperature

volume
m3

LP-0.7

0.24

150

0.2

127

0.7

LP-1.5

0.5

170

0.5

127

1.5

LP-3.5

0.5

250

0.6

170

3.5

LP-4

0.5

200

0.6

170

4

LP-5.5

0.5

250

0.6

200

5.5

LP-1.5

0.69

300

0.7

≤164

1.5

LP-3.5

0.78

350

0.9

300

3.5

LP-5.5

0.78

300

0.9

200

5.5

LP-7.5

0.78

300

0.9

250

7.5

LP-12

0.88

300

0.9

300

12

                        Note: According to user needs, various specifications of continuous arrangement can be designed, and technical parameters can be provided.
                                     
I
ntermittent blowdown flash tank
1、 The purpose of the regular discharge expansion tank is:
The periodic blowdown expansion vessel is a process of separating secondary steam and waste hot water from boiler wastewater or waste hot water discharged at a higher pressure and temperature than the periodic blowdown expansion vessel through pressure reduction and expansion. Secondary steam is discharged into the atmosphere or used as other heat sources, while waste hot water is generally discharged into the sewage system through a sewage cooling pool.
Boiler wastewater has the same working pressure and saturated water temperature as the boiler. A throttle valve is installed before the periodic discharge expander to reduce pressure, so as to expand and cool the wastewater in the periodic discharge expander, and separate the secondary steam.   

2、 Main specifications and technical parameters:

Parameter model

Design pressure MPa

Design Temperature 

Working pressure MPa

Operation temperature

Volume m3

Weight kg

DP-0.8

0.17

150

0.15

127

0.8

396.5

DP-3.5

0.17

150

0.15

127

3.5

1062

DP-7

0.17

150

0.15

127

7

1820

DP-7.5

0.17

150

0.15

127

7.5

1880

DP-7.5

0.79

300

0.69

300

7.5

2488

DP-12

0.17

150

0.15

127

12

2685

DP-16

0.69

200

0.59

≤164

16

5132

DP-35

0.17

150

0.15

127

35

6835

Note: According to user needs, various specifications of periodic discharge expansion vessels can be designed, and technical parameters can be provided.

 



 Hydrophobic expansion vessel:
1、 Purpose:
It is to expand and reduce the pressure of the hydrophobic pipeline, separate the steam and hydrophobic, and introduce the steam into the heat exchanger or deaerator to fully utilize the heat energy, while the hydrophobic is introduced into the hydrophobic tank and regularly sent to the water supply system.

2、 Structural composition: 1. Shell 2. Inlet pipe 3. Steam water separation device, etc

3、 Specifications, models, and technical parameters

Specification and model

Geometric volume
M3

Design pressure
MPa

Design Temperature

SK-0.5

0.5

0.3

300

SK-0.75

0.75

DP-1.0

1.0

SK-1.5

1.5

SK-2.0

2.0

SK-3.0

3.0

SK-5.5

5.5

SK-12.0

12.0

Note: According to user needs, various specifications of continuous arrangement can be designed, and technical parameters can be provided.
 

 

Previous article: flash tank
Next article: Filter screen of desulfurization slurry circulation pump